Victron (Ziehl) voltage and frequency relay UFR1001E
The UFR1001E network disconnection relay (MPN REL100100000) monitors voltage and frequency in AC and DC networks. Complies with the following conditions:
VDE-AR-N 4105:2018-11
- central NA protection in self-generation systems for feeding into the low-voltage grid
- Program contains 2 corresponding parameters, as well as adapted monitoring of the coupling switch and protection of parameters
- Relay is dual-channel and interference-proof
VDE-AR-N 4110:2018-11
- Unit protection at the generation units and as intermediate NA protection for feeding into the medium-voltage grid
- Can be used as higher-level NA protection if no Q-U protection is required
Features
- Undervoltage/overvoltage monitoring 15-520V (with voltage transformers up to 1000V)
- Measurement against N and/or phase-phase
- Under/overfrequency monitoring 45-65 Hz
- voltage quality monitoring (10-minute average) & zero voltage
- Alarm counter for 100 alarms (with trigger value, cause, and relative time stamp)
- Standby input with counter and time memory, remote shutdown possible
- Test button and simulation function with measurement of shutdown times
- easy commissioning and programming thanks to preset basic programs
- Preset limit values for various applications
Scope of delivery
1x Victron (Ziehl) UFR1001E